Fluoride Analyzer and Control System

The RealTech Controls Model ETX Fluoride Analyzer utilizes an ECD S80 Fluoride Ion Selective sensor that converts the analog signals from the electrode cartridge into a digital protocol that allows two-way communications with the transmitter. The identity of the sensor, measurement type, and serial number, are stored in the sensor’s memory along with three calibration registers. The large, back-lit display shows the measurement (or both measurements if dual channel), temperature, relay statuses, and mA % output. When connected to the ETX digital analyzer, the sensor’s information is uploaded to the analyzer configuring the display and outputs of the transmitter to the values appropriate to the sensor’s measured parameter.

Products

Fluoride Analyzer

Model: ETX + S80

(Fluoride Ion Selective Electrode)

Fluoride Analyzer
  • Measurement Range: 1 to 2,000 ppm Flouride
  • Temperature Range: 0°C to 80°C (32° F to 176° F)
  • Pressure Range: 0 to 50 psig (0 to 3.5 bar)
  • Response Time: T90 in 10 seconds
  • Electrode Life: 6 to 12 months
  • Interfering ions: Hydroxide, 0.1 selectivity (10 OH- = 1 F-)
  • Wetted Materials: PEEK, epoxy, LaF crystal, PTFE, 316 SS, Viton O-Ring
  • Process Connections: Insertion 3⁄4” MNPT compression fitting, or Valve Retractable: 1” MNPT Ball Valve
  • Outputs: Single or dual channel 4-20mA outputs, with optional Relays, Modbus, or HART
  • Industrial wastewater
  • Drinking water
  • Industrial effluents
  • Effluent and influent monitoring
  • Surface water
  • Process water

Accessories

It is very important that the S80 Fluoride sensor electrode remains constantly submerged in water so it does not try out.
The EMEC NPED range of probe holders is designed so that when there is minimal or no flow, water is still present in the bowl. The design of the bowl also eliminates siphoning and ensures the sensor electrode stays submerged in water. The bowl can either be installed in-line or in a side-stream sample line, depending on the amount of flow required.

Model: EMEC NPED + S80

Bowl Style Probe Holder

EMEC NPED3 with S80 Sensor
  • Ensures sensors stay submerged in water
  • Easy of Maintenance with removable Bowl
  • PP Body
  • 72 PSI at 122°F (5 Bar at 50°C)
  • Includes 6Ft Length of PE Tubing
  • Simple Installation with wall mount bracket
  • Bowls Available in Transparent or Black for outdoor installation
  • Custom options for Number of Probes, Thread Type, and Flow Switch available, contact us
  • Flow Cell accommodates 3/4″ MNPT Water Hardness Sensor
  • Additional space for 2 x 12mm smooth-body pH and/or ORP sensors
  • Custom Threads available for 3rd party probes